CATU Electrical Insulating Mats conform to IEC 61111:2009 and are manufactured using high quality elastomer rubber in order to provide complete protection against electric shock, isolating users from potentially life-threatening electrical currents.
Rigorous testing to conform to the IEC 61111:2009 standard includes:
• Puncture resistance test
• Flame retardance test
• Dielectric test • Acid resistance test
• Ageing test • Oil resistance test
-
Material: :
Elastomer, halogen free.
-
Thickness: :
2.6mm +/-0.2mm
-
Storage temperature: :
+10°C to +21°C
-
Operating temperature: :
-40°C to +55°C.
-
Insulating mat for live and dead working.
-
Class 2 - Maximum operating voltage: 17 000 V AC - 25 500 V DC.
-
Used to cover the floor for the electrical protection of operators in electrical installations.
-
Protect the workers from the ground potential.
-
Must be adapted to the nominal voltage of the network supplying the installation on which it is used.
-
In accordance with IEC 61111:2009 standard and to specific properties of the “C” Category (extremely low temperature folding test at – 40 °C).
-
RoHS2 compliant. REACH compliant (SVHC free).
-
D bar code (Datamatrix) on marking with direct link to user guide and technical sheet.